V: Ich mot un 220 kV kabel, 8 km laank, teste. Welke SR-waardering höb ich nuudig?
A: 7-stap maotprocedure: bepaol testvereistes → beraekene C → sjatte L → bereken f_res → verifiëre de beoordeilinge → herhaole → finalisere.
Stap-door-stap - 220 kV kabel, 8 km:
1. IEC 60840: V_test=2.0 × 127 kV=254 kV. Duur 60 min.
2. C ≈ 8 km × 0,2 μF/km=1.6 μF.
3. Bedink 3× 100 kV/2 A-reactors paralel: L=26.7 H, f=24.4 Hz.
4. Stroum bij 254 kV: I=V × 2πf × C=6.9 A. Maar 3×2A → 6A totaal → NEET OK.
5. Upgrade nao 3× 100 kV/4 A reactors: totaal I=12 A → OK. P_in=254×6.9/35=50 kW.
6. Totaal gewiech: 3×450 kg + 200 + 150 + 100=~1.800 kg.
Samevatting vaan de gruutde veur veurkómmende scenario’s:
|
Scenario |
V_test (kV) |
C (μF) |
f (Hz) |
Aanbevole systeem |
|
33 kV kabel, 3 km |
48 |
0.6 |
45 |
60 kV/2A ×1, 5 kW |
|
110 kV kabel, 5 km |
160 |
1.0 |
24 |
200 kV/4A ×2, 20 kW |
|
220 kV kabel, 8 km |
254 |
1.6 |
24 |
300 kV/4A ×3, 50 kW |
|
400 kV kabel, 5 km |
330 |
1.0 |
48 |
400 kV/2A ×2, 25 kW |
|
GIS 245 kV, 10 baaje |
230 |
0.05 |
80 |
300 kV/1A ×2, 5 kW |
|
Generator 100 MVA |
28 |
2.5 |
45 |
30 kV/5A, 10 kW |
Kritieke herinneringe:
• +20% marge op reactorspanningsnominale. +30% marge op stroomnominale.
• Es P_in > 100 kW, besjouw dan sectionele teste (door de mieste norme touwgestande).
• De werkeleke Q kin lieger zien es gesjat - conservatief planning vermijdt veldfoute.